TCVN 6447 | Technical specification reference, applications & PDF download

TCVN 6447 specifies technical requirements for aerial bundled cables. This cable type uses XLPE insulation and aluminum conductors, with maximum operating voltage of 0.6/1 kV for Vietnam's low voltage electrical networks.

Modern electrical transmission systems increasingly require stringent standards to ensure safety and long-term operation. Wire & cable manufacturers like Ngoc Lan Cable always strictly comply throughout the entire production process. Among these, TCVN 6447 has become a mandatory technical standard in the aluminum aerial bundled cable manufacturing process.

Ngoc Lan Cable compiles this content so engineers and specialists can reference information. The content will include:

  • General information about the standard
  • Detailed technical specification reference tables by cross-sectional area
  • Applications of the standard in electrical power and industrial projects
  • Technical FAQ responses for common questions
  • Provision of original standard PDF documents for download and storage

Let's start by understanding the nature and scope of application of this standard. Then we will delve into specific technical specifications and practical applications.

4-core compacted aluminum aerial bundled cable, XLPE insulation, TCVN 6447 standard

 

1. Introduction to TCVN 6447 Standard

To thoroughly understand the nature and scope of application of this standard, we need to grasp the following core information.

TCVN 6447 is a Vietnamese standard for aerial bundled cables. This standard specifically regulates cables using aluminum conductors and XLPE insulation, with 2, 3, or 4 cores, nominal cross-sectional areas from 16 to 150 mm² and operating voltage up to 0.6/1 kV.

TCVN 6447 is primarily applied in low voltage electrical networks. Residential and industrial projects comply with this standard to ensure operational safety.

2. Main information table

Based on the general information above, detailed reference to technical specifications becomes the next necessary step. The summary table below provides key information for quick reference.

Information Detail
Full name TCVN 6447 – Technical standard for aerial bundled cables
Scope of application Aerial bundled cables, XLPE insulation, aluminum conductors
Regulated nominal cross-section From 16 to 150mm²
Operating voltage Up to 0,6/1 kV
Year of promulgation 1998
Status Still in effect
Issuing authority Ministry of science, technology and environment

3. Technical specification reference table

After understanding the general information, referencing detailed technical specifications will provide faster support for electrical system design and construction work. The table below summarizes the technical specifications of aluminum aerial bundled cables according to TCVN 6447.

Nominal area (mm²) Structure ABC 2, 3, 4 core Approx. Max. Conductor diameter
(mm)
Nom. Thickness of insulation
(mm)
Max. Diameter of core
(mm)
Max. DC resistance at 20ºC
(Ω/km)
2C 3C 4C
16 CC CC CC 4.80 1.3 7.9 1.910
25 CC CC CC 6.10 1.3 9.2 1.200
35 CC CC CC 7.20 1.3 10.3 0.868
50 CC CC CC 8.40 1.5 11.9 0.641
70 CC CC CC 10.10 1.5 13.6 0.443
95 CC CC CC 11.90 1.7 15.9 0.320
120 CC CC CC 13.50 1.7 17.5 0.253
150 CC CC CC 14.90 1.7 18.9 0.206

These parameters are used to calculate voltage drop, determine current carrying capacity, and select protective equipment. The load capacity of the line is also evaluated based on this reference table.

Since selecting incorrect cross-sectional areas leads to overload or cost waste, engineers need to accurately reference these specifications to ensure safe operation.

4. Applications and Ngoc Lan Cable products

After mastering the technical specifications, let's explore the practical applications of aluminum aerial bundled cables applying TCVN 6447 standard in electrical power projects.

Aluminum aerial bundled cables according to TCVN 6447 are primarily applied in electrical distribution systems such as:

  • Low voltage electrical networks in urban areas – using cables with cross-sectional areas from 25mm² to 70mm²
  • Electrical projects in rural areas – prioritizing cross-sectional areas of 16mm² and 25mm²
  • Power supply for industrial clusters – commonly selecting large cross-sectional areas from 95mm² and above

To gain deeper understanding of structure and material characteristics that help optimize selection, detailed study of ABC cables will provide the specialized knowledge necessary for engineers during design and practical application processes.

5. Frequently asked questions about TCVN 6447

From deployment experience in various projects, several technical questions are commonly raised by specialists. This section addresses common concerns based on practical experience.

5.1. How to verify cables meet TCVN 6447 standard?

Check the certification documents with valid expiration dates. Measure actual cross-sectional area and compare with standard reference tables.

Poor quality cables typically have cross-sectional areas 10-15% smaller than declared specifications. Check insulation thickness using calipers.

5.2. When to choose TCVN 6447 instead of IEC 60502?

TCVN 6447 is a standard specifically for low voltage aluminum aerial bundled cables (LV-ABC), voltage rating 0.6/1kV. IEC 60502 is a standard applied to power cables with extruded insulation and accessories for rated voltages from 1kV to 30kV.

6. Download TCVN 6447 documents and product catalogue

In addition to the comprehensive reference information above, having official source documents will provide maximum support for professional work. The complete PDF documents below help you reference details when necessary.


Download Official PDF TCVN 6447

Standard document with all technical specifications, reference tables and testing methods.

Format: PDF | Size: ~820 KB

Tải file PDF


View Ngoc Lan Cable product catalogue

View details of products applying TCVN 6447 standard.

View product details

Xem catalogue

7. Summary and technical support for projects

Selecting the correct type of aerial bundled cables according to TCVN 6447 and understanding application scenarios are decisive factors for the success of all electrical projects. Through the combination of accurate technical specifications and practical construction experience, long-term operational efficiency will be ensured.

If there are specific technical requirements for projects or need for deeper discussion about electrical cable solutions, Ngoc Lan Cable's engineering team is always ready to provide support. Contact technical consulting to receive optimal solutions for your project.

0949841067
Zalo Icon
0949 841 067
Messenger Icon
Chat Facebook