CXV/S – 12/20(24)KV
Power cable, 1 core, copper conductor, conductor screen, XLPE insulated, insulation screen, metallic screen, PVC sheathed.
STANDARDS
- IEC 60228/ TCVN 6612
- IEC 60502-2/ TCVN 5935-2
TECHNICAL CHARACTERISTICS
- Rated voltage (Uo/U): 12/20(24)kV.
- Voltage test 50Hz – 5min: 42kV.
- Max. conductor temperature in normal operation: 90ºC.
- Max. conductor temperature in short-circuit for 5s max duration: 250ºC.
APPLICATION:
Used for power transmission lines and power distribution…
STRUCTURE:
1. Conductor: Copper conductor, circular compacted (class 2).
2. Conductor screen: Semi – conductive compound.
3. Insulation: XLPE.
4. Insulation screen: Semi – conductive compound.
5. Metallic screen: Copper tape.
6. Outer sheath: PVC.
MARKINGS ON CABLE:
NGOC LAN CABLE® – [YEAR] – Cu/Sc/XLPE/Sc/CTS/PVC 1C x [SIZE] mm² 12/20(24)KV – #### m
CABLE IDENTIFICATION:
Insulation: Natural color.
Outer sheath: Black or other color.
TECHNICAL SPECIFICATIONS TABLE
CC: Circular compacted conductor.
*Beside the table of specification above, the other requirements can be satisfied following to customer demand, such as, size & standards.